-  By  verifying the status of the alarm contacts on the terminals 7 to 15 of 
the Main Terminal Block (item 6 in Figure 4-6). 
-  By looking at the illuminated 1 (High alarm) and 2 (High-High alarm) push-
buttons on the enclosure door.  
 
•  H201Ci-C: No alarms. 
Table 11-2 below lists the possible states of the alarm contacts. 
Table 11-2: Possible States of the Alarm Contacts 
 
11.2.3 Operation Modes of Alarm Relays 
The mode of each alarm relay is set using the corresponding RelayMode parameter 
in  the  Hydran  201Ti’s  Relays/Analog  submenu  (or  using  the  Hydran  Host  software).  
There are four operation modes: 
•  Normal:  See Section 1.1.1.1 below. 
•  Latch:  See Section 1.1.1.2 below. 
•  Force OFF:  See Section 1.1.1.3 below. 
•  Force ON:  See Section 1.1.1.4 below. 
The  H201Ti’s  three  relays  are  independent.    A  relay  can  therefore  be  set  to  any 
operation mode regardless of the mode of the two other relays. 
1.1.1.1  Normal Mode 
In  this  mode,  the  relay  status  changes  if  an  alarm  condition  is  detected  during  a 
period of time exceeding the corresponding alarm delay; the relay returns to its former 
status when the alarm condition disappears during a period of time exceeding the same 
alarm delay.  The Normal mode is the default setting. 
In the Normal and Latch modes: 
•  The High and High-High alarm relays are energized when an alarm condition 
is detected. 
•  The  fail  alarm  relay,  however,  is  de-energized  when  an  alarm  condition  is 
detected,  to  permit  to  detect  a  power  failure  (the  relay’s  power  being 
immediately  off).    This  feature  of  the  Hydran  201i  System  strengthens  the 
security  of  the  alarm  system.    The  fail  alarm  relay  is  thus  energized  (NO 
contacts closed and NC contacts open) if no alarm condition is detected.