D.3 Hydran 201Ci-1 One-Channel Controller
Terminal
Description
From (Internal)
To (External)
Comments
1
Line or Line1
a
J2-1, ac supply
connector
Live side of
ac supply
F11 fuse:
5 A, 250 V
c
2
Neutral or
Line2
a
J2-2, ac supply
connector
Other side of
ac supply
3
Chassis
ground
(earth)
a
Connect the
P/E to the
chassis, not
to the Main
Terminal
Block
4
Auxiliary Line
or Line1
a
J2-1, ac supply
connector
Live side of
auxiliary ac
supply
5
Auxiliary Line
or Line2
a
J2-2, ac supply
connector
Other side of
auxiliary ac
supply
No fuse
installed
b
6
Auxiliary
Chassis
ground
(earth)
a
J2-3, ac supply
connector
Ground wire
of auxiliary
ac supply
7
Gas High
(Alarm 1) NO
b
J18-6, alarm
contacts
connector
Wired by the
user to a
SCADA or
RTU
Current
rating: 5A
Voltage
rating:
300Vdc
1,250 VA @
240Vac
8
Gas High
(Alarm 1)
Common
J18-5, alarm
contacts
connector
9
Gas High
(Alarm 1) NC
J18-4, alarm
contacts
connector
10
Gas High-High
(Alarm 1) NO
J18-9, alarm
contacts
connector
11
Gas High-High
(Alarm 1)
Common
J18-8, alarm
contacts
connector
Wired by the
user to a
SCADA or
RTU
Current
rating: 5A
Voltage
rating:
12
Gas High-High
J18-7, alarm