MA-033  Rev. 14.0,  12-Nov-18 
 
Hydran* 201i Instruction Manual 
 
Note:  The shield must be grounded at one end only. 
2.  Connect the cable to the main terminal block.  For wiring details, see  
Table D - 11. 
3.  Connect the cable to the SCADA system.  
 
9.3.6  Installing the Alarms Cable (Optional) 
Perform this procedure only if the Hydran 201Ci-1’s alarms are used. 
1.  Run the alarms cable through a conduit up to the SCADA system. 
2.  Connect the cable to the alarm contacts (terminals 7 to 15) of the main terminal 
block.  For wiring details, see Table D - 11. 
Note:  Do not switch heavy loads.  See the relay ratings in Table D - 11. 
3.  Connect the cable to the SCADA system. 
 
9.3.7  Installing the AC Power Supply Cable 
1.  The power supply cable of the Hydran 201Ci-1 must be connected to an external 
circuit-breaker and the installation must comply with the regulations applicable 
for  permanently  connected  equipment  in  accordance  with  local  wiring 
regulations. 
The  circuit-breaker  must  be  located  in  close  proximity  to  the 
equipment and must be easily accessible. 
The circuit-breaker must be clearly identified with a label and 
marked as the disconnecting device for the equipment. 
2.  Run the  three-wire ac. power supply  cable through  a  conduit up to the Hydran 
201Ci-1. 
3.  Connect the cable to terminals 1 and 2 of the main terminal block, and connect 
the E/G wire to the enclosure chassis.  For wiring details, see  
Table D - 11.  
4.  Connect the other end of the cable to the power source.  
Turn  off  the  electric  power  at  the  switch  or  circuit  breaker 
provided  for  disconnection  before  making  any  electrical 
connections, and  ensure  a  proper  ground  connection  is  made 
before  connecting  line  voltage.    Failure  to  do  so  can  result  in 
property damage, personal injury and/or death. 
5.  If desired, connect the H201Ti’s ac power supply cable to terminals 4 to 6 of the 
main terminal block.