alarm is triggered.  The push-button’s alarm indicator is latched; in other words, it 
remains on even if the alarm condition has disappeared and even if the alarm is 
acknowledged (using the H201Ti’s keypad or the Hydran Host software).  To turn it 
off, you must press the corresponding push-button; an alarm indicator can only 
be  turned  off  if  the  alarm  condition  has  disappeared  during  a  period  of  time 
exceeding the corresponding alarm delay (one of the alarm parameters).   
6.  Table  11-3  below  lists  the  possible  states  of  the  Hydran  201Ci-1’s  display  and 
alarm indicators. 
Table 11-3: Possible States of the Hydran 201Ci-1’s Display and Alarm Indicators 
7.  During a fail alarm, the Hydran 201Ci-1’s display is blank (see Table 11-3 above), 
and the analog outputs of the H201Ti and the H201Ci-1 drop to 4.00 ± 0.10 mA. 
8.  A message is recorded in the H201Ti’s History;Events file.  Alarm messages are 
thus stored in memory.  The Events file can contain up to 500 messages.  Each 
message comes with a set of relevant parameters (gas level, trends, etc.) and is 
identified with the recording date and time.  For details, see Section 5.5.1. 
 
11.4  Gas High and High-High Alarms 
Parameters  pertaining  to  gas  High  and  High-High  alarms  are  set  in  the  Hydran 
201Ti’s Gas submenu.  For explanations on each parameter, see Section 5.5.2. 
Set  points  for  High  alarms  should  be  adjusted  at  values  that  indicate  that  the 
transformer  (or  other  equipment)  requires  closer  monitoring.    Set  points  for  High-High 
alarms should be adjusted at values considered as critical by the user, meaning that the 
transformer requires immediate action; in general, this alarm implies an evaluation of the 
equipment and its possible removal from service. 
 
11.4.1 Alarm Parameters Setting 
1.1.1.5  Gas Level 
The gas level alarm uses the following parameters: