EasyManua.ls Logo

GE Hydran 201i - Cableshort

GE Hydran 201i
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MA-033 Rev. 14.0, 12-Nov-18
Hydran* 201i Instruction Manual
Page 180
Verify whether the HeaterTemp value in the extended Temperature submenu
displays -75°C (-103°F). If so, the heating plate thermistor cable (or a
connector in the chain of connections) is the one causing the alarm.
If the two above temperature readings are correct, execute the ForceSensor
Test command in the Service submenu. If the result is different than Good,
the sensor cable is probably the one causing the alarm.
2. Locate the corresponding cable and connectors in the Hydran 201Ti (see Section
3.4.6.2).
3. Verify thoroughly the chain of connections for this cable, including the
connectors.
4. Once the problem is fixed, execute the ForceSensor Test command in the Service
submenu to reset the H201Ti and cancel the alarm.
5. Wait at least two minutes.
6. Verify that the alarm has disappeared.
7. If applicable, verify that the corresponding temperature has returned to a normal
value.
13.1.4 CableShort
Alarm type: Fail alarm
Non-abbreviated description: Short-circuited cable
Priority: Very high (repair cable immediately)
Parameter(s) involved:
- CableShort; SysOK Relay;FaultTrig. submenu; Section 5.5.7.
- No set point nor delay
Alarm cause(s): Faulty connection with one of the following cables:
- Hydran 201 sensor cable
- Sensor thermistor cable (reading of 200°C [392°F] during one minute)
- Heating plate thermistor cable (reading of 200°C [392°F] during one
minute)
Proceed as described for the CableOpen alarm (Section 13.1.3 above), but replace the
temperature values indicated in the text by the following one: 200°C (392°F).

Table of Contents

Other manuals for GE Hydran 201i

Related product manuals