9.2.2  Initial Observations 
1.  Verify the Hydran 201Ci-1’s display is not blank. If it remains blank, the possible 
causes are as follows:  
•  If the fail alarm is triggered, read the alarm message on the  Hydran 201Ti’s 
display to identify the cause of the alarm. Then see Chapter 13. 
•  Verify the connections at both ends of the supervisory link cable. 
•  Verify the fuse(s) and the ac power supply of the H201Ci-1 and H201Ti. 
•  Verify the operation of the H201Ci-1’s display. 
2.  Verify the H201Ci-1’s display shows the same ppm value as the H201Ti’s scrolling 
gas level display.  A discrepancy of ± 2 ppm is acceptable. 
3.  Inside  the  H201Ci-1,  verify  the  Supervisory  Link  Supply  indicator  (green,  DS12; 
item 17 in Figure 4-7) is lit. 
4.  Inside the H201Ci-1, look at the Heater indicator (yellow, DS8; item 13 in Figure 4-
7): 
•  The LED must initially be lit if the ambient temperature is below approximately 
25°C (77°F). 
•  After a  while, the  LED  must  flash  as the  enclosure temperature  reaches the 
above set point. 
•  The LED must remain off if the ambient temperature exceeds the set point. 
 
5.  Since  there  are  no  alarm  conditions  present  in  the  H201Ti,  verify  the  following 
points on the H201Ci-1:  
•  The Gas High alarm  indicator of the  door-mounted  push-button 1 (item 2 in 
Figure 4-5) is off. 
•  The Gas High-High alarm indicator of the door-mounted push-button 2 (item 2 
in Figure 4-5) is off. 
•  The Alarm 1 (Gas High) indicator (yellow, DS10; item 15 in Figure 4-7) is off. 
•  The Alarm 2 (Gas High-High) indicator (yellow, DS9; item 14 in Figure 4-7) is off. 
•  The System OK indicator (yellow, DS11; item 16 in Figure 4-7) is lit. 
 
9.2.3  Verifying the Analog Output 
The Hydran 201Ci-1 is equipped with an isolated, analog 4–20 mA output.  Table 5-7 
lists  the  electrical  currents  that  should  be  generated  and  the  values  that  should  be 
displayed for each operation mode. 
1.  Proceed  as  follows:  Connect  a  dc  digital  ammeter  with  1%  accuracy  and  a 
0.01mA resolution to the main  terminal block on the H201Ci-1  (item 6 in Figure 
4-6). 
2.  Connect the positive lead on the pin 17 of the main terminal block. 
3.  Connect the negative lead on the pin 18 of the main terminal block. 
4.  On the Hydran 201Ti’s display, access the top of the extended menu by pushing 
ENTER twice (History appears). 
Note:  Once accessed, the extended menu times out after 30 minutes of keypad inactivity.