•  In the H201Ci-C:  To the DB-9 Male RS-232 Computer Port Connector J10 (item 
7 in Figure 4-3) on the circuit board. 
•  In the H201Ci-1:  To the DB-9 Male RS-232 Computer Port Connector J10 (item 
7 in Figure 4-7). 
 
 
Figure 10-2: Host Computer Connection Modes in a Hydran 201R Model i 
The installation of an RS-232 serial communication link cable is described in Section 
10.5.2. 
 
10.3.1 Local Communications using USB communication link 
One or more Hydran 201R Model is and/or Hydran 201i Systems are connected to a 
host computer using a USB communication link.  This connection can be done as follows 
(see  Figure  10-2)  by  connecting  the  host  computer  to  the  USB  Type  B  connector  of  a 
Hydran  201Ti.    In  this  case,  the  communication  can  only  be  established  with  this 
particular H201Ti.  
•  By connecting the host computer to the DB-9 or USB connector of a Hydran 
201Ci  Controller.    This  connection  gives  access  to  all  H201Ti’s  linked  to  this 
H201Ci and also, if present, to all H201Ti’s of all H201Ci’s in this local network.  
The maximum distance for an RS-232 link is 7.5m (25ft) and USB link is 5 m (16.4 ft). 
 
10.3.2 Local Communications using RS-485 serial communication link 
Starting  with  the  CPU  FW  v4.0  that  supports  both  proprietary  Hydran  protocol  and 
standard Modbus RTU protocol, up to max 32 Hydran 201Ti can be connected to a host 
computer to its USB port via a converter RS-485 to USB. An example is shown on Figure 
10-3 below. The Hydran 201Tis are connected in daisy chain over the RS-485 link.