12.2.2 Historic Data Reading 
The historic data simply consists of information (self-explanatory message, date and 
time  of  occurrence,  etc.)  recorded  by  and  within  the  Hydran  201Ti  when  an  event 
happens  (alarm  triggering,  parameter  modification  by  the  user,  etc.)  or  at  fixed, 
adjustable logging rates. 
Historic data can be read as follows: 
•  With the H201Ti local user interface: Simply access the History submenu with the 
H201Ti’s keypad.  For details, see Section 5.5.1. 
•  With the Hydran Host software or Perception software: The H201Ti’s historic data 
can be accessed easily using General Electric’s Hydran Host (for Hydran protocol 
communication  only)  or  Perception  (for  ModBus  communication  only)  software.  
Simply  transfer  the  historic  data  from  the  H201Ti’s  toward  the  Hydran  Host  or 
Perception  software  with  the  Express  Download  button  in  the  Network  Survey 
window.  The procedure is described in the Hydran Host Software Manual.  
•  With the Perception software 
 
12.3  Data Analysis 
The Hydran 201i System generates numerous data to assist in the early detection of 
incipient faults in transformers or other oil-filled equipment. 
Other  parameters  (transformer  load,  oil  temperature,  dissolved  gas  analysis  [DGA]) 
can also be  useful in interpreting  the gas level and trend  evolutions.  This information 
can even be used to comment the historic data (see the Hydran Host Software Manual). 
An  excellent  source  of  information  on  the  interpretation  of  gases  in  oil  is  the  IEEE 
Standard  C57.104-1991  “Guide  for  the  Interpretation  of  Gases  in  Oil-Immersed 
Transformers.” 
When interpreting the data of the Hydran 201i System, take the following points in 
consideration: 
•  An alarm can be triggered because of a misadjusted alarm set point.  The historic 
data file Events indicates the modifications to the parameter settings (see Section 
12.2.2 on above). 
•  An alarm (example: Low gas level) can be triggered following some maintenance 
procedure on the transformer, such as vacuum degassing of the oil. 
•  Daily load cycles and intermittent transformer operations both affect the Hydran 
201Ti’s gas level and hourly trend readings.