13.1.1 Battery L 
•  Alarm type:  Fail alarm  
•  Non-abbreviated description:  Battery voltage Low  
•  Priority:  Very low  
•  Parameter(s) involved:  
-  Batt. L; SysOK Relay; FaultTrig. submenu; Section 5.5.7. 
-  Batt.Alr L (alarm set point); Service; VoltPile submenu; Section 5.5.4.3. 
-  BattAlr Delay; Service; VoltPile submenu; Section 5.5.4.3. 
•  Alarm cause(s): Battery voltage below the Batt.Alr L alarm set point  
Replace the battery within the next nine months.  For details, see Section 3.7.3. 
 
13.1.2 Battery LL 
•  Alarm type:  Fail alarm  
•  Non-abbreviated description:  Battery voltage Low-Low 
•  Priority:  Low  
•  Parameter(s) involved:  
-  Batt. LL; SysOK Relay; FaultTrig. submenu; Section 5.5.7. 
-  Batt.Alr LL (alarm set point); Service; VoltPile submenu; Section 5.5.4.3. 
-  BattAlr Delay; Service; VoltPile submenu; Section 5.5.4.3. 
•  Alarm cause(s): Battery voltage below the Batt.Alr LL alarm set point  
Replace the battery within the next three months.  For details, see Section 3.7.3. 
 
13.1.3 CableOpen 
•  Alarm type:  Fail alarm 
•  Non-abbreviated description:  Cable open (not connected) 
•  Priority:  Very high (repair cable immediately) 
•  Parameter(s) involved:  
-  CableOpen; SysOK Relay; FaultTrig. submenu; Section 5.5.7. 
-  No set point nor delay  
•  Alarm cause(s):  Faulty connection with one of the following cables:  
-  Hydran 201 sensor cable  
-  Sensor thermistor cable (reading of -75°C [-103°F] during one minute)  
-  Heating  plate  thermistor  cable  (reading  of  -75°C  [-103°F]  during  one 
minute)  
Proceed as follows: 
1.  Identify the cable that triggers the alarm. 
•  Verify whether the SensorTemp value in the Temperature submenu displays -
75°C (-103°F).  If so, the sensor thermistor cable (or a connector in the chain of 
connections) is the one causing the alarm.