Disconnect  the  power  at  the  disconnect  switch  or  circuit 
breaker before making any electrical connections, and ensure a 
proper  ground  connection  is  made  before  connecting  line 
voltage.    Failure  to  do  so  can  result  in  property  damage, 
personal injury and/or death. 
 
3.  Because the supervisory link is isolated electrically at both ends, use it rather than 
the RS-485 link to cover long distances. 
4.  Electrical noise is one of the most important factors when selecting the location 
and installing a modem. 
5.  If the analog outputs and relay contacts must be connected to a SCADA system, it 
is  recommended  to  install  the  H201Ci  Controller  near  this  system  and  use  the 
supervisory  links  to  cover  the  distance  between  the  H201Ti’s  and  the  H201Ci 
Controller. 
•  Transmitting  the  information  using  a  supervisory  link  requires  only  three 
shielded pairs of wires (two pairs for the H201Ci-C). 
•  Transmitting  the  information  between  the  H201Ci  controller  and  the  SCADA 
system requires one RS-485 or RS-232 link cable and/or the following pairs for 
each H201Ti: 
-  Three  pairs  for  the  alarm  contacts  (High,  High-High  and  system  fail 
alarms). 
-  One or two pairs for the analog outputs. 
•  Because  of  its  digital  nature,  the  supervisory  link  provides  better  protection 
against electrical noise. 
 
6.3  Installation 
To install the components of the Hydran 201i System, please consult the following parts 
of this manual: 
•  Hydran 201Ti:  See Chapter 7. 
•  Hydran 201Ci-C: See Chapter 8. 
•  Hydran 201Ci-1:  See Chapter 9. 
•  Local network:  See Section 10.5. 
•  Optional modem:  See Section 10.6.