•  One of the  fault triggers conditions,  listed in  Table 11-1 (for details, see Section 
11.5.2 below). 
 
11.5.2 Fault Triggers 
Fault triggers are fail alarm conditions that can produce two actions: 
1.  Display of a message on the screen.  The alarm message is displayed only if the 
corresponding alarm set point is adjusted to a value; if not, it is set to OFF.  This 
setting is performed in the corresponding submenu. 
2.  Trigger  of  the  fail  alarm  relay.    Whether  the  relay  is  triggered  when  an  alarm 
condition is detected is determined in the SysOK Relay; FaultTrig. submenu.  
Note:    The  alarm  set  point  adjustment  has  priority  over  the  relay  triggering.  In  other 
words, the relay is not triggered if the alarm set point is adjusted to OFF. 
Almost all these alarm conditions have an alarm set point and an alarm delay (both 
can be  adjusted).   The  fail  alarm, for  these  conditions,  is therefore triggered the  same 
way than the gas High and High-High alarms: 
•  Low  and  Low-Low  alarms:    The  fail  alarm  is  triggered  when  one  of  the  alarm 
conditions  is  below  the  corresponding  alarm  set  point  during  a  period  of  time 
exceeding its alarm delay. 
•  High and  High-High  alarms:   The  fail  alarm  is triggered  when  one  of the  alarm 
conditions  exceeds  the  corresponding  alarm  set  point  during  a  period  of  time 
exceeding its alarm delay.  
1.1.1.8  Gas Fault Triggers 
The conditions  shown  in Table  11-7  although being  Low  and Low-Low gas  alarms, 
are classified as fail alarms because they indicate a problem of gas detection rather than 
one of gas production in the transformer.  A gas Low alarm, for example, is triggered if 
the valve on which is mounted the Hydran 201Ti is closed. 
The parameters pertaining to these alarm conditions are set in the H201Ti’s Gas and 
SysOK Relay; FaultTrig. submenus (for explanations, see Chapter 5).