Disconnect  the  power  at  the  disconnect  switch  or  circuit 
breaker before making any electrical connections, and ensure a 
proper  ground  connection  is  made  before  connecting  line 
voltage.    Failure  to  do  so  can  result  in  property  damage, 
personal injury and/or death. 
7.2.2  Initial Observations 
1.  If  the  battery  was  just  reconnected,  the  H201Ti  performs  the  first  power-up 
sequence (see Section 5.2.5.3).  Enter the requested parameters (date, time, etc.) 
using the H201Ti’s keypad. 
2.  Observe the display and ensure the H201Ti goes through the self-test sequence 
shown in Table 5-2. 
Note:  The self-test sequence is executed only if the power was down for more than five 
minutes.  Otherwise, only the message System;Initialization appears. 
Note:  A sensor test is executed at the end of the self-test sequence only if the scheduled 
last sensor test was not performed.  In this case, the H201Ti displays the message Sensor 
Good and waits 120 seconds before resuming normal display. 
3.  Verify that the H201Ti displays the Main Display mode (the parameters shown in 
Table 5-1, at the rate of one every five seconds). 
4.  Verify  the  operation  of  the  H201Ti  by  observing  the  six  small  LED  diagnostic 
indicators on the right side of the I/O module (from left to right in Figure 3-7): 
 
•   C  Heating  state  LED:    This  yellow  LED  flashes  once  every  five  seconds  in 
proportion to the amount of power supplied to the heating plate. 
-  The LED must remain lit if the internal temperature is below the set point 
(adjustable Temp SetPoint parameter in the Temperature;DynOil Sampl 
submenu).  
-  The LED must flash if the internal temperature is close to the set point.  
-  The LED must remain off if the internal temperature exceeds the set point. 
 
•  -5 - Regulated -5 Vdc supply LED:  This dim, green LED must be lit to confirm 
the presence of the -5 Vdc power supply. 
•  +5 - Regulated +5 Vdc supply LED:  This dim, green LED must be lit to confirm 
the presence of the +5 Vdc power supply. 
•  OK  -  System  state indicator  LED:  This green LED must be lit to confirm that 
the H201Ti is operating properly and that the fail alarm relay is energized.  It 
turns off if a fail alarm condition is detected  and if the  fail alarm relay is de-
energized. 
•  HH - High-High alarm state LED:  This red LED is lit when a High-High alarm 
condition  is  detected  and  the  High-High  alarm  relay  is  energized.  This  LED 
must therefore be off. 
•  H - High alarm state LED:  This red LED is lit when a High alarm condition is 
detected and the High alarm relay is energized.  This LED must therefore be off.