•  Flexible rather than rigid conduits should be used near the H201Ci-1 to ease 
installation and servicing. 
•  Conduits, or cable armors, should be made of steel to shield against magnetic 
fields. 
The procedure is as follows: 
1.  Remove the rubber plugs from the required openings of the H201Ci-1 enclosure.  
2.  For  each  cable  being  used,  install  a  standard,  watertight  conduit  fitting  (not 
supplied).  Up to six conduits may be installed (supervisory links, AC power supply 
and analog outputs). 
3.  Mount a conduit to each fitting. 
4.  Ground  the  conduits  and/or  cable  shields  at  some  point.    Follow  the  company 
regulations meticulously.  
 
9.3.4  Installing the Supervisory Link Cable 
Note:    The  supervisory  link  cable  has  already  been  run  into  conduits  up  to  the  Hydran 
201Ci-1 if the installation of the Hydran 201Ti is completed (see Section 7.3.9). 
1.  If required, trim the excess length from the end of the supervisory link cable from 
the H201Ti. 
Note:  The total maximum length of the supervisory link cable connected to one H201Ci-1 
is 1,200 m (4,000 ft). 
2.  Ensure the six have been labeled (for identification purposes) at both ends. 
3.  Connect  the  cable  wires  and  shield  to  the  H201Ci-1’s  termination  board.    For 
wiring details, see Table D - 11. 
Note:    The  shield is  grounded through a  capacitor  at  the  H201Ti  end  to protect  against 
radiofrequency  interference.    Shields  must  also  be  directly  grounded  at  the  H201Ci-1’s 
termination board. 
The  H201Ci-1’s  operation  may  be  affected  if  wires  are  not 
connected  correctly.    Be  careful  when  installing  and  inserting 
each wire.  Be sure to insert all strands in the terminal; strands 
that touch two terminals cause problems.  Strip each wire to a 
maximum of  8  mm  before  installing  it.    Do  not  leave  trims  of 
metallic strands inside the H201Ci-1’s enclosure 
 
9.3.5  Installing the Analog Output Cable (Optional) 
Perform this procedure only if the Hydran 201Ci-1’s isolated, analog 4–20 mA output is 
used. 
1.  Run  an  instrumentation-grade  cable  (twisted  pairs  with  individual  and  overall 
shields) through a conduit up to the H201Ci-1, or use an armored cable.