-  No set point nor delay  
•  Alarm cause(s):  The sensor sensitivity has dropped significantly or the sensor 
is not functioning.  
Replace sensor as soon as possible. 
Note:  The  Hydran  201Ti’s  H201  sensor  is  verified  twice  a  month  (the  first  and  fifteenth 
days of the month at midnight); the relevant parameters are recorded in the historic data 
file  Service.    This  test  can  also  be  performed  manually  using  the  ForceSensor  Test 
command  (in  the  Service  submenu),  but  no  results  are  recorded.    In  both  cases,  the 
following message is displayed if the test fails: Replace SensNOW. 
 
13.1.18  Sensor Not Inst 
•  Alarm type:  Not applicable 
•  Non-abbreviated description:  Hydran 201 sensor not installed 
•  Priority:  Very high 
•  Parameter(s) involved: None 
•  Alarm cause(s):  Problem with the H201 sensor  
This  message  can  only  be  displayed  following  the  execution  of  a  ForceSensor  Test 
command (see Section 5.5.4.2). 
Proceed as follows: 
1.  Ensure the serial numbers of the Hydran 201Ti (located at the back of the heating 
plate) and the  H201  sensor (located under the sensor connector) correspond to 
those indicated on the shipping box and on the H201Ti’s Test Certificate and Data 
Sheet.  For an example of certificate, see Figure 7-1. 
2.  Verify  whether  the  NewSensor  submenu  (Section  5.5.8)  contains  the  value 
belonging to the corresponding H201 sensor. 
3.  Press CHANGE to “force” the installation of a new sensor.  
Note:  Each H201Ti is configured for a specific H201 sensor.  If you receive more than one 
H201Ti,  take  the  necessary  precautions  to  not  interchange  the  H201  sensors  and  the 
H201Tis. 
 
13.1.19  SensTemp H 
•  Alarm type:  Fail alarm 
•  Non-abbreviated description:  Sensor temperature High 
•  Priority:  Low 
•  Parameter(s) involved:  
-  SensTemp H; SysOK Relay;FaultTrig. submenu; Section 5.5.7  
-  STempAlr H (alarm set point); Temperature submenu; Section 5.5.3 
-  TempoAlr Delay; Temperature submenu; Section 5.5.3 
•  Alarm cause(s):  Temperature of the Hydran 201 sensor above the STempAlr H 
alarm set point