12. Do  not  punch  additional  openings  in  the  H201Ci  Controller’s  enclosure.    This 
enclosure already has openings for the various cables used with the Hydran 201i 
System.  If additional openings must be made, apply a protective coating to the 
bare metal around the hole to prevent rust. 
13. Do  not  remove  the  watertight  cap  from  unused  openings  of  the  H201Ci’s 
enclosure. 
 
6.2  Installation Overview 
A typical installation of the Hydran 201i System is shown in Figure 6-8 below. Here is 
a description of each component: 
1.  Optional Hydran 201Ci Controller (Hydran 201Ci-C Communications Controller or 
Hydran 201Ci-1 One-Channel Controller) installed on vibration-absorbing rubber 
pads (see Figure 2-5). 
 
2.  Full-bore gate or ball valve. 
 
3.  Hydran 201Ti Intelligent Transmitter. 
 
4.  H201Ti’s supervisory link cable in a rigid or flexible steel conduit. 
 
5.  H201Ti’s power supply cable in a rigid or flexible steel conduit. 
 
6.  Cable for communications and analog outputs in a rigid or flexible steel conduit 
(distinct  from  alarm  cable  conduit),  toward  a  supervisory  control  and  data 
acquisition (SCADA) system. 
 
7.  Cable for alarms in a rigid or flexible steel conduit, toward a SCADA system. 
 
8.  H201Ci Controller’s power supply cable in a rigid or flexible steel conduit. 
•  All procedures in this manual must be strictly adhered to.  
Any deviation from these could cause irreversible 
damages to the transformer being monitored and/or the 
Hydran 201i System, and could lead to property damage, 
personal injury and/or death. 
•  Installation and maintenance of the Hydran 201i System 
must be carried out by qualified personnel only.