10. Install the H201Ti horizontally; not at an angle, vertically or horizontally using an
elbow (see Figure 6-6 below). Elbows may cause turbulence that can reduce the
accuracy of gas level readings. For details pertaining to the positioning of
H201Ti’s, see Section 6.2.2.3.
Figure 6-6: Do Not Install the H201Ti on an Elbow
11. Do not subject the H201Ti or its sensor to high-pressure water streams (see Figure
6-7 below). Used during the cleaning of transformers, they may cause serious
damage.
Figure 6-7: Avoid High Pressure Water Streams