Hydran* 201i Instruction Manual 
 
MA-033  Rev. 14.0,  12-Nov-18 
 
7.5  Fastening the Hydran 201Ti’s Cover 
Replace the H201Ti’s aluminum cover as soon as the installation is completed. 
1.  Ensure the rubber washer is present on the central post. 
2.  Slide the cover over the H201Ti. 
3.  Fasten  the  cover  by  tightening  the  knob.    The  breathing  membrane  must  be 
facing down (at the “6 o’clock” position) if the H201Ti is installed horizontally. 
If  connected  to  a  Hydran  201Ci  Controller,  the  H201Ti  will  later  be  used  to  test  this 
Controller. 
When  installing  the  cover,  the  knob  must  be  tightened 
correctly. After the knob touches the cover, a minimum of two 
(2) more turns  must  be applied. Failure  to  do so may  result  in 
water ingress inside the enclosure. 
7.6  Commissioning 
1.  Wait  at  least  two  hours  for  the  Hydran  201Ti  to  stabilize.    The  Hydran  201Ci 
Controller(s) can be installed during this time. 
2.  Verify  the  H201Ti’s accuracy  by  comparing  its  readings  with  a  recent  dissolved 
gas analysis (DGA). 
3.  If necessary and with the permission of the user, set the alarm set points again, 
this  time  according  to  the  current  level  of  dissolved  gases  in  oil.    See  Section 
11.4.1. 
 
The installation of the H201Ti is now completed.  If properly installed and maintained, 
the H201Ti provides many years of trouble-free service. 
 
7.7  Other Installations 
To  install  other  components  of  the  Hydran  201i  System,  please  consult  the  following 
parts of this manual: 
•  Hydran 201Ci-C: See Chapter 8. 
•  Hydran 201Ci-1:  See Chapter 9. 
•  Local network:  See Section 10.5. 
•  Optional modem:  See 10.6.