Note:  The Hydran 201Ci -C does not have alarm relays. The H201Ci-1 alarm relays are 
more accessible than the H201Ti’s relays. Generally, the H201Ci-1 alarm relays are the 
ones connected to an alarm panel or SCADA system. 
 
11.2.1 Alarm Contacts 
Each relay has: 
•  A normally open (NO) contact. 
•  A normally closed (NC) contact. 
•  A common contact (Type C). 
 
The physical form of these contacts is as follows: 
•  Hydran 201Ti:  See the Alarm Contacts 9-Terminal Block (item 12 in Figure 3-5). 
•  Hydran 201Ci -1:  See the terminals 7 to 15 of the Main Terminal Block (item 6 
in Figure 4-6). 
•  Hydran 201Ci-C:  Does not have alarm relays and thus no alarm contacts. 
 
11.2.2 Status of Alarm Relays 
The gas High and High-High alarm relays can only be in two states:  
•  On (coil energized, alarm state LED’s turned on). 
•  Off (coil de-energized, alarm state LED’s off). 
Note:    The  relays  of  the  Hydran  201Ci  Controller  always  adopt  the  state  of  the  Hydran 
201Ti’s  corresponding  relay  (except  if  the  supervisory  link  is  broken,  in  which  case  the 
H201Ci triggers a fail alarm, regardless of the H201Ti’s fail alarm relay).  As far as the fail 
alarm relay, the coil is energized in normal operation (no alarm). 
 
Table  10-1  lists  the  possible  states  of  all  relays.    The  state  of  each  relay  can  be 
determined as follows: 
•  H201Ti:  
-  By  displaying  RelayH  State,  RelayHH  State  and  SysOk  State  in  the 
Relays/Analog submenu. 
-  By looking at the LED’s on the right side of the I/O module (see Figure 3-7) 
-  By  verifying  the  state  of  the  alarm  contacts  on  the  Alarm  Contacts  9-
Terminal Block (item 12 in Figure 3-5). 
 
•  H201Ci-1:  
-  By looking at the LEDs on the circuit board (see items 13 to 18 in Figure 4-
7)