EasyManua.ls Logo

GE Hydran 201i - Alarm Contacts; Status of Alarm Relays

GE Hydran 201i
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 159
MA-033 Rev. 14.0, 12-Nov-18
Note: The Hydran 201Ci -C does not have alarm relays. The H201Ci-1 alarm relays are
more accessible than the H201Ti’s relays. Generally, the H201Ci-1 alarm relays are the
ones connected to an alarm panel or SCADA system.
11.2.1 Alarm Contacts
Each relay has:
A normally open (NO) contact.
A normally closed (NC) contact.
A common contact (Type C).
The physical form of these contacts is as follows:
Hydran 201Ti: See the Alarm Contacts 9-Terminal Block (item 12 in Figure 3-5).
Hydran 201Ci -1: See the terminals 7 to 15 of the Main Terminal Block (item 6
in Figure 4-6).
Hydran 201Ci-C: Does not have alarm relays and thus no alarm contacts.
11.2.2 Status of Alarm Relays
The gas High and High-High alarm relays can only be in two states:
On (coil energized, alarm state LED’s turned on).
Off (coil de-energized, alarm state LED’s off).
Note: The relays of the Hydran 201Ci Controller always adopt the state of the Hydran
201Ti’s corresponding relay (except if the supervisory link is broken, in which case the
H201Ci triggers a fail alarm, regardless of the H201Ti’s fail alarm relay). As far as the fail
alarm relay, the coil is energized in normal operation (no alarm).
Table 10-1 lists the possible states of all relays. The state of each relay can be
determined as follows:
H201Ti:
- By displaying RelayH State, RelayHH State and SysOk State in the
Relays/Analog submenu.
- By looking at the LED’s on the right side of the I/O module (see Figure 3-7)
- By verifying the state of the alarm contacts on the Alarm Contacts 9-
Terminal Block (item 12 in Figure 3-5).
H201Ci-1:
- By looking at the LEDs on the circuit board (see items 13 to 18 in Figure 4-
7)

Table of Contents

Other manuals for GE Hydran 201i

Related product manuals