3.  Verify  the  Hydran  201  sensor’s  serial  number  and  parameters  in  the  H201Ti’s 
Service; SensorCal Data submenu (Section 5.5.4.1). 
4.  Execute  the  H201Ti’s  ForceSensor  Test  command  (Relays/Analog  submenu)  to 
test sensor operation. 
5.  Verify the value of the HourlyTr Period parameter (period of the hourly trend; Gas; 
HourlyTrend submenu). 
6.  Verify  the  value  of  the  DailyTr  Period  parameter  (period  of  the  daily  trend; 
Gas;DailyTrend submenu). 
7.  Verify  the  value  of  the  Period  B  parameter  (Temperature;  DynOil  Sampl 
submenu). 
8.  Verify  the  parameters  pertaining  to  the  sensor  temperature  (Temperature 
submenu).  
9.  Consult General Electric to optimize the value of the parameters and the location 
of the H201 sensor. 
 
13.5.6 Inaccurate Gas Readings 
1.  Verify the transformer’s level of fault gases-in-oil by performing a dissolved gas 
analysis (DGA; see Section 14.6).  
2.  Ensure the valve (on which the Hydran 201Ti is installed) is fully open. 
3.  Confirm  that  the  valve  type  is  acceptable  (full  bore,  gate  or  ball,  no  restriction 
between valve and tank).  See the recommendations in Section 6.1. 
4.  Verify  the  Hydran  201  sensor’s  serial  number  and  parameters  in  the  H201Ti’s 
Service; SensorCal Data submenu (Section 5.5.4.1). 
5.  Execute  the  H201Ti’s  ForceSensor  Test  command  (Relays/Analog  submenu)  to 
test the sensor operation. 
6.  Verify  the  parameters  pertaining  to  the  sensor  temperature  (Temperature 
submenu).  
7.  Consult General Electric to optimize the value of the parameters and the location 
of the H201 sensor. 
 
13.5.7 Gas Level Reading is Abnormally High 
See Section 13.1.9. 
 
13.5.8 Gas Level is Slowly Decreasing towards Zero 
See Section 13.1.15.