3.7.2  Battery Specifications 
For  Hydran  201Ti  units  built  as  from  August  2014  (S/N:  1408xxxxxx),  the  battery 
specifications are the following: 
•  GE part number: 18909. 
•  Battery size and type:  Coin 24.5mm, CR2477N, Lithium 950 mAh. 
•  Recommended model: CR2477N (Renata). 
 
For Hydran 201Ti units built from 2012 (S/N: 12xxxxxxxx) to July 2014 (S/N: 1407xxxxxx), 
the battery specifications are the following: 
•  GE part number: 18877. 
•  Battery size and type:  Coin 24.5mm, CR2430, Lithium 285 mAh. 
•  Recommended model: CR2430 (Renata). 
 
Note:  For Hydran  201Ti  units,  built  in  2012  or earlier,  consult GE  Customer  Service  ((the 
coordinates can be found at the bottom of page 2). 
 
3.7.3  Removing the Battery 
It is recommended to remove the battery from the Hydran 201Ti if the unit has to be 
stored for three (3) months or more. 
Notes: 
When disconnecting the battery, only the system clock will be lost and once the battery 
has been replaced, the clock will be set to its default values (2000-01-01) 
The  system  parameters,  including  the  sensor  parameters,  the  alarm  set  points  and  the 
historic data will all be preserved when the battery is disconnected. 
To remove the battery for storage, proceed as follows: 
1.  Power off the H201Ti. 
2.  Disconnect  the  H201Ti’s  power  supply  at  the  external  switch  or  circuit 
breaker. 
3.  Remove the cover of the H201Ti unit. 
4.  Remove the two screws holding the CPU module (see item 4 of Figure 3-2). 
5.  Pull out the CPU module with care from the H201Ti. 
6.  Remove the three remaining screws. 
7.  Carefully lift off the cover of the CPU module. 
8.  Remove the battery from its holder. 
9.  Store the battery in a plastic bag.