Table 11-1: Alarm Conditions Monitored by the Hydran 201Ti 
a. Either one of the following cables (or connectors in the connection link): Sensor, sensor thermistor, or 
heating plate thermistor. 
 
11.1.2 Purpose of Hourly and Daily Trends 
Detection  of  hourly  and  daily  trend  alarm  conditions  is  a  unique  feature  of  the 
Hydran  201i  System  that  provides  early  warning  of  slowly  increasing  gas  level.    For 
example, let us consider a transformer with a 50-ppm gas level and a typical gas High 
alarm set point of 150 ppm. 
•  If no trend alarm is used and if the gas level reading starts increasing at the 
rate  of  50  ppm  per  month,  it  takes  two  months  before  the  gas  High  alarm 
condition  is  detected  and  the  investigation  of  the  possible  causes  of  the 
increase begins (unless the gas reading was already closely monitored). 
•  If  the  daily  trend  High  alarm  is  used  and  its  alarm  set  point  is  adjusted  to 
25ppm,  its  period  to  30  days  and  its  alarm  delay  to  33%  of  the  period 
(10 days), the alarm would occur approximately 23 days after the beginning of 
the gas level increase.   Investigation of the possible causes could thus start 
five weeks earlier.  For details on trend computations, see Section 11.4.3. 
11.2  Alarm Relays 
The Hydran 201Ti and the Hydran 201Ci-1 both have three alarm relays, in other words 
one relay per alarm level: 
•  One gas High alarm relay. 
•  One gas High-High alarm relay. 
•  One fail alarm relay, referred to as System in the H201Ti’s menus.