MA-033  Rev. 14.0,  12-Nov-18 
 
Hydran* 201i Instruction Manual 
 
 
The procedure is as follows: 
1.  Run the supervisory link cable into the conduit up to the H201Ci Controller, where 
it will be connected later. 
2.  Ensure all wires are identified. 
3.  Connect the cable wires and shield to the H201Ti’s supervisory link (and analog 
output) termination board. For wiring details, see Table D - 6 in Appendix D. 
4.  For the case when a local network of Hydran 201Ti has to be connected to the 
host computer: connect the RS-485 to USB converter to your PC USB port and to 
the  Hydran  201  Ti  RS-485  port  on  the  201Ti  J4  Isolated  Supervisory  Link  6-Pin 
Connector:  this connector  is  wired to the  termination board. For wiring details, 
see Table D - 6 in Appendix D. 
The  H201Ti’s  operation  may  be  affected  if  wires  are  not 
connected  correctly.    Be  careful  when  installing  and  inserting 
each wire. Be sure to insert all strands in the terminal; strands 
that touch two terminals cause problems.  Strip each wire to a 
maximum of  8  mm  before  installing  it.    Do  not  leave  trims  of 
metallic strands inside the H201Ti’s enclosure. 
5.  Connect the analog output wires to the SCADA system. 
 
7.3.10 Installing the Alarms Cable (Optional) 
If the Hydran 201Ti’s alarms are used, proceed as follows: 
1.  Run the alarms cable through the second conduit up to the H201Ti. 
2.  Connect  the  cable  to  the  H201Ti’s  Alarm  Contacts  9-Terminal  Block  (item  12  in 
Figure 3-5).  For wiring details, see Table D - 2 in Appendix D. 
3.  Connect the cable to the SCADA system. 
 
7.3.11 Installing the AC Power Supply Cable 
1.  The  power  supply  cable of the  Hydran  201Ti must  be  connected to an  external 
circuit-breaker and the installation  must comply with the regulations applicable 
for  permanently  connected  equipment  and  in  accordance  with  local  wiring 
regulations. 
The  circuit-breaker  must  be  located  in  close  proximity  to  the 
equipment and must be easily accessible. 
The circuit-breaker must be clearly identified with a label and 
marked as the disconnecting device for the equipment. 
2.  Run  the  three-wire  ac  power  supply  cable  into  the  second  conduit  up  to  the 
Hydran 201Ti.