5.5.6.5  Force Host Call 
This function is used to perform two actions: 
•  To  initialize  the  modem  in  the  H201Ci  Controller  with  the  communication  rate 
selected using the BaudRate parameter. 
•  To  test  the  communications  between  the  Hydran  201Ti  and  the  Hydran  Host 
software by forcing the H201Ci Controller’s modem to call the modem of the host 
computer where the Hydran Host is running. 
Note:  In the versions 2.1 and prior of the H201Ti embedded software, in the Call 
OnAlarm  mode,  the  telephone  number  set  in  the  modem’s  register  0  is  dialed 
automatically at midnight.  This function does not exist in version 2.2. 
5.5.6.6  H201Ti ID and PowerStation ID 
The H201Ti ID parameter is used to set the Hydran 201Ti’s identification number.  An 
exclusive identification number must be assigned to each H201Ti in a local network. 
The PowerStat ID parameter is used to set the power station’s identification number.  
The same power station identification number must be assigned to all H201Ti’s in a local 
network,  but  each  local  network  must  have  a  different  power  station  identification 
number. 
The  default  values  of  the  H201Ti  ID  and  PowerStat.  ID  parameters  are  therefore 
usually modified.    Furthermore, the  H201Ti and  power station’s  identification  numbers 
must  correspond  to  those  assigned  to  the  same  H201Ti’s  and  power  station  in  the 
Hydran Host or Perception software. 
Note:    The  identification  number  of  each  H201Ti  must  be  recorded  during  the 
configuration of the local network. 
5.5.6.7  MODBUS Address 
This  function  is  used  to  select  the  Modbus  address  and  must  be  set  to  a  numeric 
value between 1 and 255. 
This  setting  is  relevant  and  shall  be  properly  configured  only  when  the  Comm 
Channel and Default Channel are set to LocalUSB ModBus or SupervLnk MODBUS. Else, 
when 201Ti is set to Hydran protocol (Comm Channel and Default Channel are Local USB 
or Supervisory Link), this setting is ignored. 
 
5.5.7  Relays/Analog Submenu (Extended Menu Only) 
The Relays/Analog submenu is used to: