MA-033 Rev. 14.0, 12-Nov-18
Hydran* 201i Instruction Manual
Page 76
Read the state of the alarm relays: On or Off.
Set the operation mode of the three alarm relays.
Select the triggering conditions of the fail alarm (FaultTrig.).
Read the state of the analog output and TDM signal (in %).
Set the operation mode of the analog output and TDM signal.
5.5.7.1 Gas H Relay
RelayH State: Displays the status of the High alarm relay. The two possible
states are explained in Section 11.2.2.
RelayMode: Is used to set the operation mode of the High alarm relay. The four
operation modes are explained in Section 11.2.3.
5.5.7.2 Gas HH Relay
Relay HH State: Displays the status of the High-High alarm relay. The two
possible states are explained in Section 11.2.2.
RelayMode: Is used to set the operation mode of the High-High alarm relay. The
four operation modes are explained in Section 11.2.3.
5.5.7.3 SysOK Relay
SysOK State: Displays the status of the fail alarm relay. The two possible states
are explained in Section 11.2.2.
RelayMode: Is used to set the operation mode of the fail alarm relay. The four
operation modes are explained in Section 11.2.3.
FaultTrig.: Is used to set to Off or On each fail alarm condition. For details, see
Section 11.5. Press CHANGE to turn on a condition (an asterisk [*] is then
displayed at the right of the parameter’s name) or turn it off (only the parameter’s
name is displayed).
5.5.7.4 AnalogOut
AnalogState: Displays the state of the Hydran 201Ti’s analog output in
percentage of the maximum electric current. The analog output provides the gas
level being measured; the displayed percentage is thus directly proportional to
the gas level. For details on the analog output, see Section 3.5.2.
AnalogMode: Is used to set the operation mode of the analog output. The three
Force x % modes are used only to test the operation of the Hydran 201i System.
Table 5-7 shows the electrical current generated for each mode.
Operation Mode
Analog 420 mA Output
Hydran 201Ci-1 Display
Force 0%
4.00 ± 0.10 mA
0 ± 2 ppm
Force 50%
12.00 ± 0.20 mA
1000 ± 5 ppm