12. Alarm  Contacts  9-Terminal  Block  (in  Figure  3-5:    The  terminal  has  a  300-V 
rating and accepts 22–14 AWG wires (2.5 mm2 nominal).  For wiring details, 
refer to Table D - 2 in Appendix D. 
 
 
Figure 3-5: Second View of the Top Side of the I/O Module 
 
3.4.6.2  Left Side of the I/O Module 
The left side of the I/O module (Figure 3-6) supports plug connectors and the fuse.  An 
extremely  high  degree  of  electrical  and  environmental  protection  is  assured  by  a 
covering plate over the connecting zone. 
13.  J2  Heater  6-Pin  Connector:    This  connector  is  factory-wired  to  the  heating 
resistors of the Hydran 201Ti’s heating plate. For wiring details, see  Table D-4 
in Appendix D .  
14.  SW1  Voltage  Selector: For  wiring details,  see   Table  D-3  in Appendix  D.  This 
selector is used to choose between the following: 
•  115 V, corresponding to 100–120 VAC 50/60 Hz. 
•  230 V, corresponding to a 200–240 VAC 50/60 Hz. 
15. F3 AC Line Fuse:  The fuse holder is a standard 5 x 20 mm holder. 
16. J3 AC Line 3-Pin Connector:  This connector is factory-wired to the line filter.