3.4.6.1  Top Side of the I/O Module 
The top side of the I/O module supports five components: 
8.  AC Power 3-Terminal Block (in Figure 3-4):  The terminal has a 300-V rating and 
accepts 22–14 AWG wires (2.5 mm2 nominal).  For wiring details, see Table D – 
1 in Appendix D. 
9.  Supervisory  Link  and  Analog  Output  Termination  Board  (in Figure 3-4 below): 
The  terminal  has  a  300-V  rating  and  accepts  26–14  AWG  wires  (1.5  mm
2
 
nominal).  It is protected against surge and electromagnetic interference.  For 
wiring details, see Table D - 6 in Appendix D. 
Note:  The  Hydran  201R  Model  i  uses  a  9-m  (30-ft)  6-conductor  cable  for  the 
supervisory link.  Other configurations use either 4- or 6-conductor cables of varying 
lengths. 
10.  AC  Line  EMI  Filter  (in  Figure  3-4  below):    The  line  filter,  located  beneath  the 
Supervisory  Link  and  Analog  Output  Termination  Board  (item  9),  blocks  the 
electromagnetic interferences conducted in the ac power supply. 
 
Figure 3-4: First View of the Top Side of the I/O Module 
 
11.  Thermostat  (in  Figure  3-5  below):    It  stops  the  heating  whenever  the  base 
plate temperature exceeds 100 °C.