MA-033 Rev. 14.0, 12-Nov-18
Figure 3-6: Left Side of the I/O Module
17. J5 Alarm Relays 9-Pin Connector: This connector is factory-wired to the alarm
contacts terminal block.
18. J4 Isolated Supervisory Link 6-Pin Connector: This connector is wired to the
termination board. For wiring details, see Table D - 6 in Appendix D.
19. J3 Local Analog Output 4-Pin Connector: This connector is wired to the
supervisory link terminal block. The 420 mA output is isolated. For wiring
details, see Table D - 6 in Appendix D.
20. J2 Thermistor 2-Pin Connector: This connector is factory-wired to the heating
plate thermistor. For wiring details, see Table D - 5 in Appendix D.
21. J1 Sensor 4-Pin Connector: This connector is factory-wired to the Hydran 201
sensor. For wiring details, see Table D - 5 in Appendix D.
3.4.6.3 Right Side of the I/O Module
The right side of the I/O module (Figure 3-7) carries six small LED diagnostic
indicators.
22. ˚C Heating state LED: This yellow LED flashes once every five seconds in
proportion to the amount of power supplied to the heating plate.
The LED remains lit if the internal temperature is below the set point
(adjustable Temp SetPoint parameter in the Temperature; DynOil Sampl
submenu).