MA-033 Rev. 14.0, 12-Nov-18
Terminal
Description
From (Internal)
To (External)
Comments
32
Loop supply(+),
input
J12-1, supervisory
link connector No. 2
regulator
input
into
H201Ci
33
Cable shield
Chassis
Supervisory
link cable
shield of
unit No 2
Direct
ground
connection
34
Not used
35
36
Serial data(-),
I/O unit No. 1
J15-3, supervisory
link connector No. 1
Isolated
RS485
transceiver
Must be
connected
to H201Ti
37
Serial data(+),
I/O unit No. 1
J15-4, supervisory
link connector No. 1
38
Loop supply(-),
input
J15-2, supervisory
link connector No. 1
Isolated
+5Vdc
regulator
input
Isolated
supply built
into
H201Ci
39
Loop supply(+),
input
J15-1, supervisory
link connector No. 1
40
Cable shield
Chassis
Supervisory
link cable
shield of unit
No 1
Direct
ground
connection
a: Wires have a maximum section of 2.5 mm2.
b: An isolating, double-pole breaker must be installed in accordance with IEC 947-1 and
947-3 standards.
Table D - 8: Main Terminal Block for the Hydran 201Ci-C
Voltage Selector
a
Voltage Range
Comment
115V
100120 VAC, 50/60 Hz
130W maximum heating
@ 264 VAC
230V
200240 VAC, 50/60 Hz
a: The voltage selector is factory-selected and configured as per user requirements
Table D - 9: SW1 Voltage Selector for the Hydran 201Ci-C