Hydran* 201i Instruction Manual 
 
MA-033  Rev. 14.0,  12-Nov-18 
 
Historic data verification (Section 14.5) 
Dissolved gas analysis (DGA; Section 14.6) 
Hydran 201Ti verification (Section 14.7): 
•  Visual inspection 
•  LED’s, heater, display and keypad verification (Section 7.2.2) 
•  Parameter verification (alarm set points, etc.) 
•  Alarm relays verification (Section 7.2.4) 
•  Verification of sensor tests
a
 (Section 7.2.6) 
•  Analog output verification (if connected; Section 7.2.8) 
Annually or on fail 
alarm 
Hydran 201Ci Controller verification (Section 14.8): 
•  Visual inspection 
•  LED’s, heater and display verification (Section 9.2.2) 
•  Hydran 201Ci-1’s analog output verification (if connected; 
Section 9.2.3) 
•  H201Ci-1’s alarm relays verification (if connected; Section 
9.2.4)  
•  RS-232 or USB and RS-485 communications verification 
(Section 8.2.3) 
Annually or on 
fail alarm 
a.  The H201Ti’s sensor is tested automatically twice a month, and the results are stored in the historic data 
file Service.  
Table 14-1: Maintenance Routines and their Frequency