MA-033 Rev. 14.0, 12-Nov-18
Hydran* 201i Instruction Manual
Page 236
Category
Parameter
Unit
Value
Status
Temperature
Desired temperature
˚C
35
Modulation amplitude
˚C
10.0
Period A
Minutes
120
Low-Low alarm
˚C
5
Enabled
Low alarm
˚C
15
Enabled
High Alarm
˚C
65
Enabled
High-High Alarm
˚C
75
Enabled
Alarms delay
Minutes
30
Battery
Low-Low alarm
Volt
2.45
Enabled
Low alarm
Volt
2.75
Enabled
Alarms delay
Hours
50
Historical data
acquisition
Short term log rate
Minutes
15
Long term log time #1
00:00
Long term log time #2
06:00
Enabled
Long term log time #3
12:00
Enabled
Long term log time #4
18:00
Enabled
Communications
CommChannel
Supervisory Link
DefaultChannel
Supervisory Link
CommMode
Call on Alarm
BaudRate
9600
H201Ti ID
PowerStat. ID