MA-033 Rev. 14.0, 12-Nov-18
Table J - 4: Function codes
In order to promote the interoperability of systems, the coils and discrete inputs are
accessed as the same digital data objects. For the same reason, the input and holding
registers are also accessed through the same 16-bit data objects. An unsupported
function code addressed to the Hydran 201Ti slave returns an Illegal Function Code
exception response code of 01; see Section J.3.2 on page 252 for more details.
J.3.1.1 Read Coils (01h) / Read Discrete Inputs (02h)
This function is used to read a binary value. Up to 2,000 (07D0h) consecutive binary
can be read per request. Table J-5 shows the format of the master and slave packets.
Note: This Section demonstrates how to build and understand a 01h or 02h Modbus
request/response exchange. To read or write Hydran 201Ti’s digital data values,
please refer to the subsequent Sections.
Modbus Date Type
Referred as
Function Code (hex)
Read coil status
Read Binary
01
Read discrete input status
02
Read holding registers
Read Analog
03
Read input register
04
Force single coil
Write Binary
05
Force multiple coils
0F
Preset single holding register
Write Analog
06
Preset multiple holding registers
10