3-81
CHAPTER 3 Settings and Measurement
(2)-13 Backup setting
This device has a function to periodically back up recorded data.
(Refer to the gure below.)
GL980
FTP server
Ethernet
Automatic backup to an FTP server
Measurement input
Auto backup to SD memory card or USB memory
SD CARD
x GB
Lock
(1)
(2)
(3)
Setting Description
(1) Backup intervals Set the interval to back up the captured data.
Off, 1, 2, 6, 12, 24 hours ;specied time
(2) Backup Destination Set the backup destination of the captured data.
Internal memory : The data is backed up to the internal memory of the device.
SD card : The data is backed up to the SD card.
USB memory : The data is backed up to the USB memory.
FTP : Backs up data to an FTP server on the network.
* Capturing destination and backup destination cannot be the same.
* When SD card or USB memory is selected as backup destination, SD card and USB memory
can be replaced. For details, refer to "3.5 Setting Menus" - "7. File menu".
* The FTP server settings must be made using the Interface settings.
(Refer to "FTP/WEB server settings".)
(3) Save folder Set the folder to save the backup le.
* This must be a folder on the Internal memory,SD card,USB memory or an FTP server.
Example) \GRAPHTEC\¥20171001
If ring capture is On, the backup function is not available.
WhensettotheCSVleformat,thesamplingintervalisfrom10ms.
Toreplacethebackupdestinationmedia,besuretoexecutetheRemove/ReplaceintheFilemenubefore
replacing.
IfthesamplingtimeisfasterbecausethenumberofeffectiveCHsislarge,orthebackupintervalislonger,
thesizeofthedatatobebackedupincreases,soitmaytaketimetonishwritingatthetimeofcapturing
stop.
WhensavingtoanFTPserver,backupmayfaildependingonthecommunicationenvironmentandtransfer
speed.