5.6 Battery Life/ Usage Tracking
l
Alkaline Battery Item 48 tracks the Battery voltage and Item 49 is the configurable Low Limit
for tripping a low Battery Alarm condition. Item 50 is the configurable Low Limit for putting the
EC350 in to a low Battery ‘shutdown’ condition ending most of its operations to greatly
conserve the battery power.
l
Lithium Battery - Items 1001 and 1002 indicate the remaining months and percentage of the
Lithium Battery pack based on estimated ‘usage cycles’. Item 59 tracks the battery usage cycles
but only for a limited amount (mainly for testing purposes). Item 60 is the configurable Low
Limit for tripping a low Battery Alarm condition based on too high of battery usage cycles. Item
59 value represents micro-Amp-seconds usage of the Battery.
Battery / External Supply Alarms RBX Mode
l
Non-RBX Mode (Item 165 = 0) No automatic clearing of alarm condition. User must clear
(acknowledge) the alarm condition of Item 99 or 796 before a new Alarm Log entry or timestamp
update can be made for any subsequent Low Voltage Alarm conditions.
l
RBX Mode (Item 165 = 1)- RBX Mode enabled will allow for automatic clearing of a Low Voltage
alarm condition of Item 99 or 796 if the measured voltage reaches a value greater than 0.60
VDC above the Low Limit value in Item 49 or 795 respectively (Battery or External Voltage).
5 Key features
5.6 Battery Life/ Usage Tracking
Honeywell 2024
99

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell EC350 and is the answer not in the manual?

Honeywell EC350 Specifications

General IconGeneral
BrandHoneywell
ModelEC350
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals