Monitoring and Operating the Controller 
106  UDC2500 Universal Digital Controller Product Manual  4/07 
Configuration Check for Duplex 
See Subsection 3.6 - Accutune Set Up Group for details. 
Make sure: 
•  TUNE has been enabled 
•  DUPLEX has been configured to Manual, Automatic or Disabled 
4.11.3  Using AUTOMATIC TUNE at start-up for Duplex (Heat/Cool) 
Used when DUPLEX has been configured for AUTOMATIC.  This is the preferred 
selection for most Heat/Cool applications when tuning a new chamber.  This selection 
will sequentially perform both Heat and Cool tuning without further operator 
intervention. 
Table 4-12  Procedure for Using AUTOMATIC TUNE at Start-up for Duplex Control 
Step  Operation  Press  Result 
1 
Configure LSP1 
Lower
Display
Lower
Display
Lower
Display
 
Until SP (Local Setpoint 1) shows 
in the lower display. 
2 
 
or  
Until LSP1 is a value within the 
Heat Zone (output above 50%). 
3 
Configure LSP2 
Lower
Display
Lower
Display
Lower
Display
 
Until 2SP (Local Setpoint 2) shows 
in the lower display. 
4 
 
or  
Until LSP2 is a value within the 
Cool Zone (output below 50%). 
5 
Switch to 
“Automatic” Mode 
M-A
Reset
M-A
Reset
M-A
Reset
 
Until the “A” indicator is lighted (on 
controllers with Manual option). 
6 
Show Tuning 
Prompt 
Lower
Display
Lower
Display
Lower
Display
 
Until “NoTUNE” is shown on lower 
display. 
7 
Initiate Tuning 
 
Select “DoSLOW” or “DoFAST” in 
lower display. 
 
Tuning in operation 
Lower
Display
Lower
Display
Lower
Display
 
Upper display will flash “TUNE” as 
long as ACCUTUNE process is 
operating.  When process 
completes, tuning parameters are 
calculated and lower display will 
show “NoTune” prompt. 
 
4.11.4  Using BLENDED TUNE at start-up for Duplex (Heat/Cool) 
When DUPLEX has been configured for DISABLE.  This is the preferred selection for 
Heat/Cool applications which use a highly insulated chamber (a chamber which will lose 
heat very slowly unless a cooling device is applied).  Only one local setpoint (LSP 1) is 
needed for this selection.