EasyManua.ls Logo

Honeywell UDC2500 - Input 2 Set up Wiring; Table 5-11 Set up Wiring Procedure for 0 to 20 Ma or 4 to 20 Ma Inputs - Input 2; Figure 5-8 Wiring Connections for 0 to 20 Ma or 4 to 20 Ma Input - Input 2

Honeywell UDC2500
243 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input Calibration
146 UDC2500 Universal Digital Controller Product Manual 4/07
5.6 Input 2 Set Up Wiring
0 to 20 mA or 4 to 20 mA Inputs – Input 2
Refer to Figure 5-8 and wire the controller according to the procedure given in Table
5-13.
Table 5-11 Set Up Wiring Procedure for 0 to 20 mA or 4 to 20 mA Inputs –
Input 2
Step Action
1
Connect the copper leads from the calibrator to the Input #2 terminals as shown in
Figure 5-8.
2
Place current source at zero before switching on.
3
Do not switch current source ON/OFF while connected to the instrument.
25+
26 (no connection)
27-
Copper Leads
Equal Length
Current
Source
+
_
25+
26 (no connection)
27-
Copper Leads
Equal Length
Current
Source
+
_
Figure 5-8 Wiring Connections for 0 to 20 mA or 4 to 20 mA Input – Input 2

Table of Contents

Other manuals for Honeywell UDC2500

Related product manuals