Modbus Read, Write and Override Parameters plus Exception Codes 
214  UDC2500 Universal Digital Controller Product Manual  4/07 
10.7.11 Alarms 
Table 10-19 lists all the register addresses and ranges or selections for the function 
parameters in Set-up Group Alarms. 
Table 10-19  Set-up Group – Alarms 
Parameter 
Description 
Register 
Address 
Data 
Type 
Access  Data Range or 
Enumerated Selection 
  Hex  Decimal       
Alarm 1 Setpoint 1 
Value 
0009  009  FP  R/W  Within the range of 
selected parameter or PV 
span for deviation alarm 
Alarm 1 Setpoint 2 
Value 
000A  010  FP  R/W  Within the range of 
selected parameter or PV 
span for deviation alarm 
Alarm 2 Setpoint 1 
Value 
000B  011  FP  R/W  Within the range of 
selected parameter or PV 
span for deviation alarm 
Alarm 2 Setpoint 2 
Value 
000C  012  FP  R/W  Within the range of 
selected parameter or PV 
span for deviation alarm 
Alarm 1 Setpoint 1 
Type 
008C 140  INT  R/W 
0 = None 
1 = Input 1 
2 = Input 2 
3 = PV 
4 = Deviation 
5 = Output 
6 = Alarm on Shed 
7 = SP Event On 
8 = SP Event Off 
9 = Manual 
10 = Remote Setpoint 
11 = Failsafe 
12 = PV Rate of Change 
13 = Alarm on Digital 
Input 1 
14 = Alarm on Digital 
Input 2 
15 = Loop Break 
16 = Deviation based upon 
SP2 
17 = T/C Warning 
18 = T/C Fail