Configuration 
4/07  UDC2500 Universal Digital Controller Product Manual  51 
3.8  Output Set Up Group 
Introduction 
This group deals with various output types in the controller, the Digital Output Status and 
the Current Output operation. 
 ATTENTION The Tuning Group is automatically configured to have two PID sets 
when a Duplex Control Algorithm is selected. 
Function Prompts 
Table 3-8 OUTPUT Group (Numeric Code 500) Function Prompts 
Function Prompt  
Lower Display 
Selection or Range of Setting 
Upper Display 
English  Numeric 
Code 
English  Numeric 
Code 
Parameter  
Definition 
OUTALG 
501 
 
 
The OUTPUT ALGORITHM lets you select 
the type of output you want. Not applicable 
with Control algorithm prompt TPSC 
(Three Position Step Control). 
Selections are hardware dependent. For 
example, if the controller does not have a 
current output, then none of the prompts for 
Output Algorithms that need a current output 
will appear. Likewise, if the controller does 
not have a relay output, then none of the 
prompts that need a relay output will appear. 
 ATTENTION  For all Duplex Output forms, 
PID heat parameters apply for controller 
output greater than 50 %; PID cool 
parameters apply for controller output less 
than 50 %. 
 
RLY 
0 
TIME SIMPLEX—This output algorithm uses 
Digital Output 1 for Time Proportional 
Control. The output is updated per the Loop 
sampling rate selection. Time Proportional 
Output has a resolution of 4.44 msec. Cycle 
Time is adjustable from 1 to 120 seconds. 
 
RLY2 
1 
TIME SIMPLEX—This output algorithm uses 
Digital Output 2 for Time Proportional 
Control. The output is updated per the Loop 
sampling rate selection. Time Proportional 
Output has a resolution of 4.44 msec. Cycle 
Time is adjustable from 1 to 120 seconds.