Monitoring and Operating the Controller 
124  UDC2500 Universal Digital Controller Product Manual  4/07 
Function  Press  Result 
Viewing the present 
ramp or soak 
segment number 
and time 
Lower
Display
Lower
Display
Lower
Display
 
until you see 
Upper Display = PV value 
Lower Display = XXHH.MM 
Time remaining in the SEGMENT in hours and 
minutes.  XX = The current number, 1 to 12. 
Viewing the number 
of cycles left in the 
program 
Lower
Display
Lower
Display
Lower
Display
 
until you see 
Upper Display = PV value 
Lower Display = REC_XX 
Number of cycles remaining in the setpoint 
program.  X = 0 to 99 
End Program 
 
When the final segment is completed, the 
“RUN” in the upper display either changes to 
“HOLD” (if configured for HOLD state), or 
disappears (if configured for disable of setpoint 
programming). 
•  The controller either operates at the last 
setpoint in the program or goes into manual 
mode/failsafe output. 
Disable Program    See Section 
3 – Configuration Group 
“SPPROG” for details. 
 
Power outage 
 ATTENTION   If power is lost during a program, upon power-up the controller will be in 
hold and the setpoint value will be the setpoint value prior to the beginning of the 
setpoint program. The program is placed in hold at the beginning. The mode will be as 
configured under “PWR UP” in the “CONTROL” group. 
 
Digital input (remote switch) operation 
Program can be placed in RUN or HOLD state through a remote dry contact connected to 
optional digital input terminals, as follows: 
RUN—contact closure places Program in RUN state, OR 
HOLD—contact closure places Program in HOLD state 
Opening the contact will cause the Controller to revert to its original state.