Output Calibration
4/07 UDC2500 Universal Digital Controller Product Manual 157
Step Operation Press Result
Upper Display = the new selection
Lower Display = CRANGE (for the Current Output)
- or -
Lower Display = ARANGE (for the Auxiliary Output)
or
to change the range selection in the upper display back to the
proper selection. You will see:
Upper Display = Original range selection
Lower Display = CRANGE (for the Current Output)
- or -
Lower Display = ARANGE (for the Auxiliary Output)
4
Return to Normal
Operation
Lower
Display
Lower
Display
Lower
Display
to return to Normal operating mode.
The factory calibration will be restored. If the problem is not
corrected, contact the Honeywell Technical Assistance Center at 1-
800-423-9883 USA and Canada