Modbus Read, Write and Override Parameters plus Exception Codes
4/07 UDC2500 Universal Digital Controller Product Manual 199
Parameter
Description
Register
Address
Data
Type
Access Data Range or
Enumerated Selection
Hex Decimal
Controller Status
at Program End
00B4 180 INT R/W 0 = Last Setpoint and Mode
1 = Manual, Failsafe Output
Reset SP Program
(ToBEGIN)
00B3 179 INT R/W 0 = Disable
1 = Via Keypad
PV Hotstart 00E2 226 INT R/W
0 = Disabled
1 = Enabled
Segment #1 Ramp
Time
0039 057 FP R/W 99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #2 Soak
Setpoint Value
003A 058 FP R/W Within Setpoint Limits
Segment #2 Soak
Time
003B 059 FP R/W 99.59 (0-99 Hrs:0-59 Min)
Segment #3 Ramp
Time
003C 060 FP R/W 99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #4 Soak
Setpoint Value
003D 061 FP R/W Within Setpoint Limits
Segment #4 Soak
Time
003E 062 FP R/W 99.59 (0-99 Hrs:0-59 Min)
Segment #5 Ramp
Time
003F 063 FP R/W 99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #6 Soak
Setpoint Value
0040 064 FP R/W Within Setpoint Limits
Segment #6 Soak
Time
0041 065 FP R/W 99.59 (0-99 Hrs:0-59 Min)
Segment #7 Ramp
Time
0042 066 FP R/W 99.59 (0-99 Hrs:0-59 Min)
or
0 to 999 (Degrees/Minute)
Segment #8 Soak
Setpoint Value
0043 067 FP R/W Within Setpoint Limits