Configuration 
54  UDC2500 Universal Digital Controller Product Manual  4/07 
Function Prompt  
Lower Display 
Selection or Range of Setting 
Upper Display 
English  Numeric 
Code 
English  Numeric 
Code 
Parameter  
Definition 
RLY TYP 
 
 
 
MECH 
S S 
 
 
0 
1 
RELAY CYCLE TIME INCREMENT 
selection is used only for Time Simplex and 
Duplex output configurations. This 
configuration sets the increment size of the 
relay cycle times in the Tuning and Tuning 2 
Set Up groups. 
ELECTROMECHANICAL RELAY—Cycle 
time in one-second increments. 
SOLID STATE RELAY—Cycle time in 1/3 
second increments. This is useful for solid 
state relay applications that require shorter 
cycle times. DO NOT use this setting unless 
cycle times of less than 1 second are 
required. 
 ATTENTION  The Lockout selection must 
be set to NONE in order to view this 
selection. 
MTR TI  505 
5 to 1800 seconds 
 
MOTOR TIME – Appears only when “TPSC” 
(Three Position Step Control) is selected as 
the Control Algorithm.  This is the time it 
takes the motor to travel from 0 to 100 % 
(fully closed to fully open).  This time can 
usually be found on the nameplate of the 
motor.