Configuration 
68  UDC2500 Universal Digital Controller Product Manual  4/07 
Function Prompt  
Lower Display 
Selection or Range of Setting 
Upper Display 
English  Numeric 
Code 
English  Numeric 
Code 
Parameter  
Definition 
 
DEV 4 
DEVIATION (PROCESS VARIABLE 
MINUS SETPOINT)—Represents –100 % 
to +100 % of the selected PV span in 
engineering units. 
Zero deviation will produce a center scale 
(12 mA or 50 %) output. A negative deviation 
equal in magnitude to the Auxiliary Output 
High Scaling Factor will produce a low end 
output (4 mA or 0 %) output.  A positive 
deviation equal in magnitude to the Auxiliary 
Output Low Scaling Factor will produce a 
high end output (20 mA or 100 %). 
FOR EXAMPLE: 
  Input 1 = Type T High Thermocouple 
  PV range = –300 °F to +700 °F 
  PV span = 1000 °F 
  Deviation Range = –1000 °F to +1000 °F 
  Auxiliary Output Low Scale Value = 0.0 
  Auxiliary Output High Scale Value = 1000 
 
  If PV = 500 °F and SP = 650 °F 
  then Deviation Display = –150 °F, which 
is  
  –7.5% of the Deviation Range, so 
  Auxiliary Output = 50% – 7.5% = 42.5% 
 
OUT 5 
OUTPUT—Represents the displayed 
controller output in percent (%). Cannot be 
used with 
Three Position Step Control. 
 
SP 6 
SETPOINT—Represents the value of the 
setpoint currently in use and is shown in the 
same units as those used by the PV. 
 
LSP 1  7 
LOCAL SETPOINT ONE—Auxiliary output 
represents Local Setpoint 1 regardless of 
active setpoint. 
 
LSP 2  8 
LOCAL SETPOINT TWO—Auxiliary output 
represents Local Setpoint 2 regardless of 
active setpoint. 
0PCT 902 
Value in 
Engineering Units 
 
AUXILIARY OUTPUT LOW SCALING 
FACTOR— This is a value in engineering 
units used to represent all AUX OUT 
parameters except Output. 
For Output, this is a value in percent and can 
be any value between –5 % and +105 %.  
However, keep in mind that relay output 
types can only be scaled 0 % to 100 %.