Configuration 
4/07  UDC2500 Universal Digital Controller Product Manual  71 
Function Prompt  
Lower Display 
Selection or Range of Setting 
Upper Display 
English  Numeric 
Code 
English  Numeric 
Code 
Parameter  
Definition 
 
 TIMR 
12 
TIMER—Contact closure starts timer, if 
enabled. Reopening the switch has no 
effect. 
 
 TUNE 
13 
INITIATE LIMIT CYCLE TUNING—Contact 
closure starts the slow tuning process. The 
lower display shows DoSLOW. Opening the 
contact has no effect. 
 
 INIT 
14 
SETPOINT INITIALIZATION—Contact 
closure forces the setpoint to the current PV 
value. Opening the contact has no effect. 
 
 RSP 
15 
TO REMOTE SETPOINT—Contact closure 
selects the Remote setpoint. 
 
 MNLT 
16 
MANUAL LATCHING—Contact closure 
transition forces the loop to Manual mode. 
Opening the switch has no effect. If the M-A 
RESET key is pressed while the switch is 
closed, the loop will return to Automatic 
mode. 
 
 TRAK 
17 
OUTPUT TRACKS INPUT 2—Contact 
closure allows Output to track Input 2. While 
the switch is open, the output is in 
accordance with its pre-defined functionality. 
When the switch is closed, the output value 
(in percent) will track the Input 2 percent of 
range value. When the switch is reopened, 
the output will start at this last output value 
and normal PID action will then take over 
control. The transfer is bumpless. 
 
 STRT 
18 
PV HOTSTART—Contact closure starts the 
SP Ramp or SP Program at the original 
selected starting Setpoint Value that existed 
at the time that the SP Ramp or Program 
was first started. Opening contact has no 
effect. This configuration must be selected 
prior to the first time the SP Ramp or 
Program is placed in the RUN mode, as 
otherwise the unit will not be able to capture 
the initial Setpoint value. This selection 
allows the unit to retain the initial Setpoint 
value even if power to the unit is lost. 
When the STATE selection in the SP Ramp 
or Program Set Up group is set to HOLD and 
the digital input contact is left closed, then 
when the end of the program or ramp is 
reached, the program or ramp will