Appendix A Parameters Shenzhen Hpmont Technology Co., Ltd.
116 HD5L-PLUS Series User Manual V1.0
Function
Setting Range Default
Unit
Attribute
Setting
F20.13
Elevator enable function quickly
detects on
0: Do not open
1: Open
0 1
×
F20.14
UPS running undervoltage
setting
170 - 220V 190V 1V
×
F20.15
Judgment method of light load
current in emergency operation
Unit: Emergency operation
light load current search up
and down switch brake
control
0: Not close the holding
brake
1: Close the holding brake
Ten: Emergency operation
torque limit
0: F20.19 does not work
1: F20.19 works
Hundred: Emergency
operation mode
determination
0: Determined by F00.01
1: V/f control
Thousand, ten thousand:
Unused
111 1
×
F20.16
Detection method of light load
current in emergency operation
0: According to the output
current
1: According to the state
change of electric power
generation
0 1
×
F20.17
Search speed of light load current
method in emergency operation
0.020 - 0.200m/s 0.100m/s 0.001m/s
×
F20.18
Search time of light load current
in emergency operation
0.300 - 3.000s 0.500s 0.001s
×
F20.19
Torque limit in mergency
operation
70.0 - 200.0% 100.0% 0.1%
×