Parameter Description Remarks
PV module type This parameter is used to set dierent
types of PV modules and the shutdown
time of the concentration PV module. If
the concentration PV modules are shaded,
the power drops drastically to 0 and the
inverter shuts down. The energy yield
would be
aected since it takes too long
for the power to resume and inverter to
restart. The parameter does not need to be
set for crystalline silicon and
lmy PV
modules.
● If this parameter is set to
Crystalline silicon or Film,
the inverter automatically
detects the power of PV
modules when they are
shaded and shuts down if the
power is too low.
● When concentration PV
modules are used:
– If this parameter is set to
CPV 1, the inverter can
quickly restart in 60
minutes if the input power
of PV modules drops
drastically due to shading.
– If this parameter is set to
CPV 2, the inverter can
quickly restart in 10
minutes if the input power
of PV modules drops
drastically due to shading.
Built-in PID
compensation
direction
When the external PID module
compensates the PID voltage for the PV
system, set Built-in PID compensation
direction to the actual compensation
direction of the PID module so that the
inverter can output reactive power at
night.
Built-in PID compensation
direction must be consistent
with PV module compensation
voltage direction of the PID
module.
PID running
mode
Species the operation mode of the
inverter built-in PID.
-
PID nighttime
o-grid repair
Species whether to enable the PID
nighttime o-grid repair.
If PID running mode is not set
to Disable, the parameter can
be set.
PID daytime o-
grid repair
Species whether to enable the PID
daytime o-grid repair.