Parameter Description Remarks
String connection
mode
Species the connection mode of PV
strings.
When PV strings connect to
the inverter separately (All PV
strings separated), there is no
need to set this parameter.
The inverter can
automatically detect the
connection mode of the PV
strings.
When PV strings connect to
one another in parallel
outside the inverter and then
connect to it independently
(All PV strings connected), set
this parameter to All PV
strings connected.
Automatic OFF
due to
communication
interrupted
The standards of certain countries and
regions require that the inverter must shut
down after the communication is
interrupted for a certain time.
If Automatic OFF due to
communication interrupted is
set to Enable and the inverter
communication is interrupted for
a specied time (set by
Communication interruption
duration), the inverter will
automatically shut down.
Communication
interruption
duration (min)
Species the duration for determining
communication interruption. Used for
automatic shutdown for protection in case
of communication interruption.
-
Automatic ON
due to
communication
resumed
If this parameter is set to Enable, the
inverter automatically starts after
communication recovers. If this parameter
is set to Disable, the inverter needs to be
started manually after communication
recovers.
This parameter is displayed
when Automatic OFF due to
communication interrupted is
set to Enable.
Soft start/boot
time (s)
Species the duration for the power to
gradually increase when the inverter starts.
-
Shutdown
gradient (%/s)
Species the power change speed when
the inverter shuts down.
-
AFCI The North American standard requires that
the inverter should have DC arc detection
function.
-
AFCI detection
adaptive mode
Adjusts the sensitivity of arc detection. This parameter is displayed only
when AFCI is set to Enable.
AFCI self-test Send the AFCI self-check command
manually.
-
SmartLogger3000
User Manual 6 WebUI Operations
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 125

Table of Contents

Other manuals for Huawei SmartLogger3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SmartLogger3000 and is the answer not in the manual?

Huawei SmartLogger3000 Specifications

General IconGeneral
BrandHuawei
ModelSmartLogger3000
CategoryData Loggers
LanguageEnglish

Related product manuals