Reactive Power Fix Control
Parameter Description
Reactive power control
mode
If the PV array is required to generate constant
reactive power at a specied time, set this parameter
to Reactive power x control.
Start time If the device is required to run with specied
maximum power in certain periods of a day, add
setting records based on site requirements.
When multiple time points are set, the device will run
with the maximum power specied for the time point
that is earlier than and the closest to the current
system time. For example, if you add 00:00:00 and
12:00:00 on the WebUI and the current system current
is 14:30:00, the device will run with the maximum
power
specied for 12:00:00.
Reactive power (kVar)
Power Factor Fix Control
Parameter
Description
Reactive power control
mode
If the PV plant is required to generate a constant
power factor at the grid-connection point and the
device is required to adjust the real-time reactive
power based on the preset power factor, set this
parameter to Power factor x control.
Start time If the device is required to run with a specied power
factor in certain periods of a day, add setting records
based on site requirements.
When multiple time points are set, the device will run
with the maximum power specied for the time point
that is earlier than and the closest to the current
system time. For example, if you add 00:00:00 and
12:00:00 on the WebUI and the current system current
is 14:30:00, the device will run with the maximum
power
specied for 12:00:00.
Power factor
Q-U Characteristic Curve
If you do not need the SmartLogger to send remote reactive power control
commands, you can
congure the characteristic curve as a substitute. The
SmartLogger delivers the values congured for the characteristic curve to the solar
inverter, which then operates according to the conguration. The SmartLogger no
longer adjusts the values.