Parameter Description
Shut down solar
inverter upon reactive
power scheduling
timeout
The default value is Disable. If this parameter is set to
Enable, the SmartLogger shuts down the device when
the communication between the SmartLogger and the
scheduling backend is interrupted for a period longer
than the set value of Reactive power scheduling
timeout threshold for triggering solar inverter
shutdown.
Reactive power
scheduling timeout
threshold for triggering
solar inverter shutdown
The default value is 300. This parameter is used only
for shutdown protection for reactive power scheduling
when the communication between the SmartLogger
and the scheduling backend is abnormal. If the
communication is interrupted for a period longer than
the set value, it is determined as abnormal.
Start up solar inverter
upon recovery from
reactive power
scheduling timeout
The default value is Enable. If this parameter is set to
Enable, after a reactive power scheduling timeout
occurs, if the reactive power scheduling recovers, the
device automatically starts.
Limit solar inverter
power upon reactive
power scheduling
timeout
The default value is Disable. If this parameter is set to
Enable, the SmartLogger controls the device in the
following ways after the communication between the
SmartLogger and the scheduling backend is
interrupted for a period longer than the set value of
Reactive power scheduling timeout threshold for
triggering solar inverter power limiting.
Limit the reactive power of the inverter based on
the value of Q/S during power limiting of solar
inverter in case of reactive power scheduling
timeout.
Limit the reactive power of the PCS based on the
value of Q/S during power limiting of ESS in case
of reactive power scheduling timeout.
Reactive power
scheduling timeout
threshold for triggering
solar inverter power
limiting (s)
The default value is 300.0. This parameter is used only
for reactive power limiting protection when the
communication between the SmartLogger and the
scheduling backend is abnormal. If the
communication is interrupted for a period longer than
the set value, reactive power limiting protection is
started.
SmartLogger3000
User Manual 6 WebUI Operations
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 215

Table of Contents

Other manuals for Huawei SmartLogger3000