Alarm
ID
Alarm Name Alarm
Severity
Alarm
Sub-ID
Cause Suggestions
1135 The SDS
license
capacity is
insucient
Major 1 The license
capacity of
the smart
tracker is
insucient.
Contact your dealer to apply for
a license le and reload the
license le. Ensure that the
license capacity of the intelligent
tracing algorithm is greater than
or equal to the actual rated
power of the subarray.
1136 Abnormal
communicati
ons
Major 1 The
communicati
ons cable is
abnormal.
Stop the cable connection check,
turn o the DC and AC switches
in the power distribution cabinet.
Wait for 5 minutes. Verify that
no electricity is present with a
multimeter before checking the
FE communications cable
connection.
1251 SmartModule
Certicate
Invalid
Warning 1 The
SmartModule
digital
signature
certicate is
invalid.
Check the time or change the
digital signature certicate.
1252 SmartModule
Certicate
About to
Expire
Warning 1 The
SmartModule
digital
signature
certicate is
about to
expire.
Change the digital signature
certicate in time.
1253 SmartModule
Certicate
Expired
Major 1 The
SmartModule
digital
signature
certicate has
expired.
Change the digital signature
certicate immediately.
1140 Black Start
Fail
Minor 1 The black
start
command is
not delivered
in the correct
time
sequence.
The sequence of the black start
instructions does not comply
with the black start
implementation of the array.
Contact the microgrid controller
vendor to correct the sequence
of black start instructions.
SmartLogger3000
User Manual 7 Device Maintenance
Issue 10 (2022-08-20) Copyright © Huawei Technologies Co., Ltd. 240