6.4 Parameter function descriptions
6-9
6. Parameters
Parameter No.4: Home position adjustment
No.
Category
Name
Symbol Unit Input range
Default setting
at shipping
4 B
Home position
adjustment
OFST mm 0.01 to 9999.99
According to
ELECYLINDER
specifications
Sets the distance between the home side mechanical stopper and the home position.
The minimum setting unit is 0.01mm.
Adjustment with this parameter is possible in the following situations.
(1) To match the ELECYLINDER home position and the mechanical home position after assembly
into equipment.
(2) To adjust the new home position upon reversing the default home return direction after purchase.
(3) To eliminate a slight deviation from the previous home position generated after replacing the
ELECYLINDER.
If [Parameter No.4] is [0.30mm],
the relationship between mechanical stopper and home position is as follows.
Caution
If adjusting Parameter No.4, simultaneously adjust Parameter No.1.
Operation range adjustment with parameter No.1 uses the home position as reference.
Do not set Parameter No.4 to a value smaller than the default setting at shipping.
This may result in abnormal home return operation, alarm triggering or abnormal
operation. If the value must be set small, please contact IAI.
After changing this parameter, always perform home return reset (absolute reset).
Configuration example
0.30mm 0.30mm
80.00mm
(Stroke to be used)
Parameter No.4: 0.30mm
Home position

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IAI EC-RR6*AH series and is the answer not in the manual?

IAI EC-RR6*AH series Specifications

General IconGeneral
BrandIAI
ModelEC-RR6*AH series
CategoryController
LanguageEnglish

Related product manuals